SETTING OBSTRUCTION FORCE
CHECKING LIMITS POSITIONS
WARNING: If gates require sync delay - Switch 1 must be set to
ON before fine tuning limits.
1. Re-engage drive units.
2. Press OSC to move gate until the limit switch engages.
3. Fine tune limts cam positions so that the gate reaches the
desired open and closed positions.
NOTE: In the pre-initialised state the OSC button moves the gate
only while depressed.
IMPORTANT NOTICE:
Intialising must be performed for the gates obstruction sensors to
be correctly calculated and to set the soft stop feature.
SYNCHRONISED OVERLAPPING GATE LEAFS
When dual swing gates are used it is common for a back stop to
be mounted on one of the gate leafs so that the leafs are aligned
when closed. To prevent the gate leafs from interfering with each
other, the gate leaf with the back stop must reach the close
position first when closing and open last.
Set “SYNCHRONISING DELAY” dip-switch to “ON” position.
This will result in the M1 starting to open 2 seconds before M2
and M2 starting to close 2 seconds before M1.
Note:If a lock is to be fitted to the gate, it should be mounted on
the leaf driven by M1. If the delay of 2 seconds is not suitable it
can be altered, see sections SYNCHRONISING DELAY TIME.
on page 16.
INITIALISING OBSTRUCTION FORCE
WARNING: Make sure that the obstruction sensitivity is
adjusted correctly so that, when obstructed with minimum
pressure, the gate(s) reverse to the open position and stops on
opening cycle.
In order for the controller to slow the motors down at the correct
position and to automatically detect overloads, it needs to record
the normal cycle time of each motor in each direction and also
sample each motors normal running time. If the gate(s) is stopped
for some reason during step 2 below, then simply restart the
process. While the open and close cycles are underway, the
control board will not slow the motors and the overload detection
is disabled.
INITIALISATION
1. Engage the motor assembly (Fig. 3 & 4), switch power on at
power point. Replace drive unit cover and lock in place.
2. Close the gate(s) if it is not already closed, by holding down
the OSC button. Once the gate(s) is in the fully closed
position release OSC button. The Red LED should be
steady ON.
3. Press the Reset button on the control board for about two
seconds then release. The gate(s) should start opening. When
the gate(s) reaches the fully open position it will pause and
start to close. When the gate(s) returns to the fully closed
position the initialisation is complete. The controller is now
ready for normal use.
NOTE: The OSC button is the only input which will function
prior to the controller being initialised using the above procedure.
SETTING OVERLOAD SENSITIVITY
The overload sensitivity is adjustable using the OVERLOAD dial.
Position 0 making it easy to overload a motor, increasing through
positions 1 to 8, with position 9 being the hardest. To set, turn the
dial to the desired number to manually increase or decrease the
overload sensitivity.
Standard default is - 5. Areas prone to high wind may require a
slight increase.
NOTE: The gate will exert some force before obstruction sensing
activates. Too light a setting will cause nuisance stopping when
gate starts to age or resistance occurs in gate track rollers or
hinges. Too heavy a setting may cause serious personal injury
and/or property damage.
WARNING: Force adjustment must be set correctly and tested
upon completion of installation. The gate should be tested
periodically to ensure correct operation and adjustment made as
required. The opener must not be used if force setting is incorrect
or inoperative.
NOTE: Whenever the limit cams are adjusted the safety
obstruction system must be cleared and re-initialised as travel
distance may have changed.
MOTOR SPEED CONTROL
At the start of the gate’s cycle the selected motor speed is set
using the SPEED dial with 0 being the slowest and 9 being the
fastest. The motor will be driven at this speed until it nears the end
of the travel, at which time it will be slowed down. The motor
slows down to the speed represented by '3' on the speed dial.
NOTE: Setting the dial to 3 or lower will negate the soft stop
function.
In order for the controller to determine when to slow the motors
down towards the end of its cycle, a complete open and close
cycle must be performed and the travel times of each motor in
each direction established (i.e. initialisation).
To adjust the slow motor speed refer to page 16.
13